| SCOTCH
MARINE : DRYBACK : 300
SERIES : SPECIFICATION DATA CHART |
 |
 |
 |
| BOILER
SPECIFICATIONS (ALL DIMENSIONS ARE IN INCHES) |
| |
BOILER
HORSEPOWER |
15 |
20 |
25 |
30 |
40 |
50 |
60 |
70 |
80 |
100 |
|
| |
HEATING SURFACE |
FIRESIDE |
SQ. FT. |
75 |
100 |
125 |
150 |
200 |
250 |
300 |
350 |
400 |
500 |
|
| STEAM OUTPUT |
FROM & @212°F |
LB/HR |
517 |
690 |
862 |
1035 |
1380 |
1725 |
2070 |
2415 |
2760 |
3450 |
| GROSS OUTPUT |
|
MBH |
502 |
670 |
837 |
104 |
1339 |
1675 |
2008 |
2343 |
2687 |
3348 |
| FIRING RATE, GAS |
1,000
BTU/CFH |
CFH |
630 |
840 |
1050 |
1260 |
1680 |
2100 |
2520 |
2940 |
3360 |
4200 |
| FIRING RATE, LP GAS |
91,500
BTU |
GPH |
6.9 |
9.2 |
11.5 |
13.8 |
18.4 |
23 |
27.5 |
32.1 |
36.7 |
45.9 |
| FIRING RATE, No.2 oil |
140,00O
BTU |
GPH |
4.5 |
6 |
7.5 |
9 |
12 |
15 |
18 |
20.7 |
24 |
30 |
| FIRING RATE, #5 & #6
OIL |
150,000
BTU |
GPH |
4.2 |
5.6 |
7 |
8.4 |
11.2 |
14 |
16.8 |
19.3 |
22.4 |
28 |
| A |
*NOTE: 1 STEAM OUTLET
SIZE |
150 PSI |
IN |
1 1/4 |
1 1/4 |
1 1/4 |
1 1/2 |
1 1/2 |
2 |
2 |
2 1/2 |
2 1/2 |
3 |
A |
| A |
*NOTE: 2 STEAM OUTLET
SIZE |
15 PSI |
IN |
2 1/2 |
3 |
3 |
4 |
4 |
4 |
6 |
6 |
6 |
6 |
A |
| B |
*NOTE: 2 WATER SUPPLY
SIZE |
30 PSI |
IN |
2 1/2 |
3 |
3 |
3 |
4 |
4 |
4 |
6 |
6 |
6 |
B |
| C |
*NOTE: 2 WATER RETURN
SIZE |
30 PSI |
IN |
2 |
2 1/2 |
3 |
3 |
3 |
3 |
4 |
4 |
4 |
6 |
C |
| D |
FEEDWATER CONNECTION |
|
IN |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 1/4 |
1 1/4 |
1 1/4 |
D |
| E |
BLOWDOWN CONNECTION
(VESSEL) |
BOTTOM |
IN |
1 |
1 |
1 |
1 |
1 1/4 |
1 1/4 |
1 1/4 |
1 1/4 |
(2) 1
1/2 |
(2) 1
1/2 |
E |
| F |
STACK OUTLET SIZE OD. |
|
IN |
8 |
8 |
10 |
10 |
12 |
12 |
12 |
16 |
16 |
16 |
F |
| G |
FURNACE OD. |
|
IN |
16 |
16 |
18 |
18 |
20 |
20 |
20 |
24 |
24 |
24 |
G |
| H |
SHELL ID. |
|
IN |
36 |
36 |
42 |
42 |
48 |
48 |
48 |
54 |
54 |
54 |
H |
| I |
WIDTH WITHOUT TRIM |
|
IN |
44 |
44 |
50 |
50 |
56 1/2 |
56 1/2 |
56 1/2 |
62 |
62 |
62 |
I |
| J |
WIDTH WITH TRIM |
|
IN |
49 |
49 |
55 |
55 |
61 |
61 |
61 |
68 |
68 |
68 |
J |
| K |
LENGTH, FRONT TO REAR |
|
IN |
69 |
84 |
78 |
89 |
99 |
119 |
135 |
117 |
129 |
153 |
K |
| L |
LENGTH OVERALL |
|
IN |
103 |
118 |
113 |
124 |
134 |
154 |
170 |
155 |
167 |
191 |
L |
| M |
SKID LENGTH |
|
IN |
72 |
90 |
84 |
96 |
102 |
120 |
138 |
117 |
132 |
150 |
M |
| N |
SKID WIDTH |
|
IN |
30 |
30 |
36 |
36 |
40 |
40 |
40 |
44 |
44 |
44 |
N |
| O |
STEAM SUPPLY LOCATION |
|
IN |
29 |
26 |
30 |
35 |
40 |
48 |
48 |
53 |
53 |
67 |
O |
| P |
WATER SUPPLY LOCATION |
|
IN |
18 |
24 |
23 |
27 |
30 1/2 |
30 1/2 |
36 |
36 |
33 |
39 |
P |
| Q |
WATER RETURN LOCATION |
|
IN |
45 |
56 |
51 |
59 |
68 |
84 1/2 |
84 |
78 |
87 |
105 |
Q |
| R |
BLOWDOWN LOCATION |
15 PSI & UP |
IN |
18 |
17 |
18 |
18 |
23 |
23 1/4 |
23 1/4 |
25 |
25 -
66 |
25 -
89 |
R |
| S |
1 1/4" SURFACE BLOW-OFF
CONNECTION |
|
IN |
41 |
50 |
36 |
53 |
61 |
39 |
40 |
45 |
41 |
51 |
S |
| T |
STACK OUTLET LOCATION |
|
IN |
58 |
73 |
66 |
77 |
86 |
106 |
122 |
102 |
114 |
138 |
T |
| U |
SUPPLY HEIGHT |
|
IN |
51 |
51 |
57 |
57 |
63 |
63 |
63 |
71 |
71 |
75 |
U |
| V |
STACK HEIGHT |
|
IN |
54 1/2 |
54 1/2 |
60 1/2 |
60 1/2 |
68 5/8 |
68 5/8 |
68 5/8 |
77 |
77 |
76 3/4 |
V |
| W |
SHELL TO FLOOR HEIGHT |
|
IN |
12 |
12 |
12 |
12 |
12 |
12 |
12 |
14 |
14 |
14 |
W |
| X |
BURNER PROJECTION |
|
IN |
32 |
32 |
32 |
32 |
32 |
32 |
32 |
32 |
32 |
36 |
X |
| Y |
DOOR SWING |
|
IN |
0 |
0 |
23 |
23 |
28 |
28 |
28 |
31 |
31 |
31 |
Y |
| AA |
TUBE REMOVAL |
REAR |
IN |
32 |
47 |
39 |
50 |
58 |
78 |
94 |
66 |
78 |
102 |
AA |
| BB |
TUBE REMOVAL |
FRONT |
IN |
41 |
56 |
48 |
59 |
63 |
83 |
99 |
73 |
85 |
109 |
BB |
| |
WATER CAPACITY @ NWL |
|
GAL. |
123 |
165 |
193 |
233 |
330 |
425 |
502 |
436 |
510 |
628 |
|
| WATER CAPACITY FLOODED |
|
GAL. |
146 |
195 |
225 |
271 |
383 |
493 |
582 |
528 |
606 |
761 |
| APPROX. SHIPPING WEIGHT
(HIGH PRESS.) |
150 PSI |
LBS. |
2975 |
3225 |
3850 |
4125 |
6100 |
7375 |
8250 |
9400 |
10300 |
12450 |
| APPROX. SHIPPING WEIGHT
(LOW PRESS.) |
15 & 30
PSI |
LBS. |
2850 |
3075 |
3650 |
3925 |
5750 |
6950 |
7550 |
8100 |
9300 |
11100 |
| |
BOILER
HORSEPOWER |
15 |
20 |
25 |
30 |
40 |
50 |
60 |
70 |
80 |
100 |
|
|
| BOILER
SPECIFICATIONS (ALL DIMENSIONS ARE IN INCHES) - CONTINUED |
| |
BOILER
HORSEPOWER |
150 |
200 |
250 |
300 |
350 |
400 |
500 |
600 |
700 |
800 |
|
| |
HEATING
SURFACE |
FIRESIDE |
SQ.
FT. |
750 |
1000 |
1250 |
1500 |
1750 |
2000 |
2500 |
3000 |
3500 |
4000 |
|
| STEAM
OUTPUT |
FROM & @212°F |
LB/HR |
5175 |
6900 |
8625 |
10350 |
12075 |
13800 |
17250 |
20700 |
24150 |
27600 |
| GROSS
OUTPUT |
|
MBH |
5021 |
6695 |
8369 |
10042 |
11716 |
13390 |
16738 |
20085 |
23432 |
26780 |
| FIRING
RATE, GAS |
1,000
BTU/CFH |
CFH |
6300 |
8400 |
10500 |
12600 |
14700 |
16800 |
21000 |
25200 |
29400 |
33600 |
| FIRING
RATE, LP GAS |
91,500
BTU |
GPH |
68.8 |
91.8 |
114.7 |
137.7 |
160.6 |
183.6 |
229.5 |
275.4 |
321 |
367 |
| FIRING
RATE, No.2 oil |
140,00O
BTU |
GPH |
45 |
60 |
75 |
90 |
105 |
120 |
150 |
180 |
210 |
240 |
| FIRING
RATE, #5 & #6 OIL |
150,000
BTU |
GPH |
42 |
56 |
70 |
84 |
98 |
112 |
140 |
168 |
196 |
224 |
| A |
*NOTE:
1 STEAM OUTLET SIZE |
150
PSI |
IN |
4 |
4 |
6 |
6 |
6 |
6 |
6 |
8 |
8 |
8 |
A |
| A |
*NOTE:
2 STEAM OUTLET SIZE |
15
PSI |
IN |
8 |
8 |
10 |
10 |
10 |
12 |
12 |
12 |
12 |
12 |
A |
| B |
*NOTE:
2 WATER SUPPLY SIZE |
30
PSI |
IN |
8 |
8 |
8 |
10 |
10 |
10 |
12 |
12 |
12 |
12 |
B |
| C |
*NOTE:
2 WATER RETURN SIZE |
30
PSI |
IN |
6 |
6 |
6 |
8 |
10 |
10 |
10 |
10 |
12 |
12 |
C |
| D |
FEEDWATER
CONNECTION |
|
IN |
1 1/2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
D |
| | |