The
Cyclone Hot Water Boilers provide for exceptionally high efficiencies, lower
fuel costs, and extremely rugged construction.
Other features include:
- Compact space
saving vertical design
- Four-Pass
Design
- Shock Proof,
no tubes to loosen or burn out
- Convenient
access to eye high burner
- Solid State
controls for trouble free operation
- Factory assembled,
fully automatic
- UL and ASME
CSD - 1
- Simple and
inexpensive to install
- Standard
design pressure of 30 PSI
Optional to 160 PSI, 250° F
|
 |
| CYCLONE
SERIES SPECIFICATIONS |
| |
BOILER
HORSEPOWER |
6 |
10 |
15 |
20 |
25 |
30 |
40 |
50 |
60 |
70 |
80 |
100 |
|
| |
GROSS OUTPUT |
(MBH),
BTU X 1000
KCAL X 1000 |
201
51 |
335
84 |
502
127 |
670
169 |
837
211 |
1004
253 |
1339
337 |
1674
422 |
2009
506 |
2343
590 |
2678
675 |
3348
844 |
|
| INPUT REQUIRED |
BTU X
1000
KCAL X 1000 |
251
63.3 |
418
105 |
628
158 |
837
211 |
1046
264 |
1255
316 |
1674
422 |
2092
527 |
2511
633 |
2929
738 |
3348
844 |
4184
1054 |
| FIRING RATE, NAT. GAS
1000 BTU/FT3 |
FT 3/HR.
M 3/HR. |
251
7.1 |
418
11.8 |
628
17.8 |
837
23.7 |
1046
29.6 |
1255
35.5 |
1674
47.4 |
2092
59.2 |
2511
71.1 |
2929
82.9 |
3348
94.8 |
4184
118.5 |
| FIRING RATE, LP. GAS
91,500 BTU/GAL. |
GPH
LPH |
2.7
10.4 |
4.6
17.3 |
6.9
26 |
9.1
34.6 |
11.4
43.3 |
13.7
51.9 |
18.3
69.2 |
22.9
86.6 |
27.4
103.9 |
32
121.2 |
36.6
138.5 |
45.7
173.1 |
| FIRING RATE, No.2 oil
140.000 BTU/GAL. |
GPH
LPH |
1.8
6.8 |
3
11.3 |
4.5
17 |
6
22.6 |
7.5
28.3 |
9
33.9 |
12
45.3 |
14.9
56.6 |
17.9
67.9 |
20.9
79.2 |
23.9
90.5 |
29.9
113.1 |
| A |
OUTLET SIZE |
IN.
MM |
2
51 |
2
51 |
2
51 |
3
76 |
3
76 |
4
102 |
4
102 |
6
152 |
6
152 |
6
152 |
6
152 |
6
152 |
A |
| B |
RETURN SIZE |
IN.
MM |
2
51 |
2
51 |
2
51 |
2.5
64 |
2.5
64 |
3
76 |
3
76 |
4
102 |
4
102 |
4
102 |
4
102 |
4
102 |
B |
| C |
DRAIN SIZE |
IN.
MM |
1
25 |
1
25 |
1
25 |
1
25 |
1
25 |
1.25
32 |
1.25
32 |
1.25
32 |
1.25
32 |
1.5
38 |
1.5
38 |
1.5
38 |
C |
| D |
STACK DIA. |
IN.
MM |
8
203 |
8
203 |
8
203 |
8
203 |
8
203 |
10
254 |
12
305 |
12
305 |
12
305 |
14
356 |
14
356 |
14
356 |
D |
| E |
STACK HEIGHT |
IN.
MM |
52
1321 |
52
1321 |
58
1473 |
64
1626 |
64
1626 |
63
1600 |
73
1854 |
83
2108 |
83
2108 |
82
2083 |
82
2083 |
82
2083 |
E |
| F |
WIDTH WITHOUT TRIM |
IN.
MM |
35.2
894 |
35.2
894 |
35.2
894 |
35.2
894 |
35.2
894 |
41
1041 |
50
1270 |
59
1499 |
59
1499 |
68
1727 |
68
1727 |
78.2
1986 |
F |
| G |
WIDTH WITH TRIM |
IN.
MM |
42
1067 |
42
1067 |
42
1067 |
42
1067 |
42
1067 |
47
1194 |
55
1397 |
63
1600 |
63
1600 |
72
1829 |
72
1829 |
82
2083 |
G |
| H |
OVERALL HEIGHT |
IN.
MM |
70
1778 |
70
1778 |
76
1930 |
82
2083 |
82
2083 |
82
2083 |
93
2362 |
105
2667 |
105
2667 |
106
2692 |
106
2692 |
106
2692 |
H |
| I |
HEIGHT WITHOUT TRIM |
IN.
MM |
65
1651 |
65
1651 |
71
1803 |
77
1956 |
77
1956 |
77
1956 |
88
2235 |
98
2489 |
98
2489 |
98
2489 |
98
2489 |
98
2489 |
I |
| J |
LENGTH |
IN.
MM |
60
1524 |
60
1524 |
60
1524 |
60
1524 |
60
1524 |
78
1981 |
87
2210 |
115
2921 |
115
2921 |
120
3048 |
120
3048 |
127
3226 |
J |
| |
WATER CAPACITY |
GALS.
LITERS |
62
235 |
62
235 |
68
257 |
79
299 |
79
299 |
113
428 |
208
787 |
313
1185 |
313
1185 |
440
1665 |
440
1665 |
591
2237 |
|
| SHIPPING WEIGHT |
LBS.
KG. |
1600
726 |
1600
726 |
1750
794 |
1800
816 |
1800
816 |
2175
987 |
3775
1712 |
5300
2404 |
5300
2404 |
7300
3311 |
7300
3311 |
8700
3946 |
| |
BOILER
HORSEPOWER |
|
6 |
10 |
15 |
20 |
25 |
30 |
40 |
50 |
60 |
70 |
80 |
100 |
|
|
| Outlet connection over four
inches are 150# flanges. All other connections are NPT. We assume no responsibility