LPE Series

| Firing Rate | Water Capacity | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| HP | Heating Surface Fireside (SQ. FT.) |
Steam Output @212°F (LB/HR) |
Gross Output (MBH) |
Gas 1,000 BTU (CFH) |
LP Gas 91,500 BTU (GPH) |
#2 Oil 140,000 BTU (GPH) |
#5 Oil 150,000 BTU (GPH) |
@NWL (GAL) |
Flooded (GAL) |
Approx. Weight |
|
| LPE-20 | 20 | 100 | 690 | 670 | 840 | 6 | 120 | 141 | 2952 | ||
| LPE-30 | 30 | 132 1/2 | 1035 | 1004 | 1260 | 9 | 163 | 191 | 3670 | ||
| LPE-40 | 40 | 165 1/2 | 1380 | 1339 | 1680 | 12 | 209 | 245 | 4332 | ||
| LPE-50 | 50 | 200 | 1725 | 1674 | 2100 | 15 | 194 | 255 | 4342 | ||
| LPE-60 | 60 | 246 | 2070 | 2009 | 2520 | 18 | 239 | 313 | 5046 | ||
| LPE-70 | 70 | 291 | 2415 | 2343 | 2940 | 21 | 306 | 394 | 5875 | ||
| LPE-80 | 80 | 336 | 2760 | 6578 | 3360 | 24 | 333 | 434 | 6597 | ||
| LPE-100 | 100 | 400 | 3450 | 3348 | 4200 | 30 | 390 | 508 | 7464 | ||