Two pass dry back scotch marine boiler. Two pass design eliminates refractory baffles between flue gas passes. Minimum maintenance with rugged construction for extra-long life. Efficiencies allow for burning number 5 and number 6 oil with complete combustion with low heat release.
Available in Steam or Hot Water Versions | 15 - 800 HP Pressures to 300 psig
-
Two-pass design eliminates refractory baffles between flue gas passes.
-
Minimum maintenance with rugged construction for extra-long life.
Standard Features
-
Boiler is of the two-pass, scotch type, built and stamped in accordance with the requirements of the ASME Code, and listed by the National Board of Boilers and Pressure Vessel Inspectors.
-
Large combustion chamber with low heat release for complete combustion.
-
Smoke box is front-mounted with slip-on stack connector.
-
Access to fireside is accomplished with hinged and davited rear door (40 HP & larger) and with split front doors. Flame observation ports are on front and rear.
-
Openings for cleanout inspection of waterside are provided with 3” x 4” hand holes, and with 12” x 16” manholes (80 HP up).
-
Insulated with 2” high-density mineralwool, lagged with 22 gauge grip jacketing, baked on epoxy enamel to resist chipping and fading.
-
Firetubes are rolled and beaded on power boilers, expanded and flared on low pressure boilers (2” dia. through 30 HP, 2 1/2” dia. 40 HP and up).
-
Supports include lifting lugs securely welded to the top of shell; structural steel support legs on skids support the boiler so that special foundations are not required.
Standard Steam Trim
-
Operating & limit pressure control
-
Modulating pressure control (when appl.)
-
Water column with gauge glass, M-M 157 combination low water cut-off & pump control
-
Probe Aux, L.W.C.O.
-
Steam pressure gauge, syphon & test cock
-
Water column drain valve
-
Safety relief valve(s) per ASME Code
Standard Water Trim
-
Operating & limit temperature control
-
Modulating temperature control (when appl.)
-
Probe type low water cut-off control
-
Combination pressure, temperature, altitude gauge
-
Hot water return baffle for shock resistance
-
Safety relief valve(s) per ASME Code