| BOILER
SPECIFICATIONS (ALL DIMENSIONS ARE IN INCHES) |
| |
BOILER
HORSEPOWER |
100 |
125 |
150 |
175 |
200 |
225 |
|
| |
HEATING SURFACE (FIRESIDE)
SQ. FT. |
358 |
358 |
358 |
358 |
358 |
358 |
|
| STEAM OUTPUT, FROM & AT
212¤ F. LBS./HR. |
3450 |
4313 |
5175 |
6037 |
6900 |
7762 |
| GROSS OUTPUT MBH |
3348 |
4184 |
5021 |
5858 |
6695 |
7532 |
| FIRING RATE, GAS (1,000
BTU/CF) CFH |
4200 |
5250 |
6300 |
7350 |
8400 |
9450 |
| FIRING RATE, LP GAS
(91,500 BTU) GPH |
46 |
57 |
69 |
80.5 |
92 |
103 |
| FIRING RATE, No.2 oil
(140,000 BTU) GPH |
29.9 |
37.4 |
45 |
52.5 |
60 |
67.3 |
| FIRING RATE, #5 & 6
OIL (150,000 BTU) GPH |
28 |
35 |
42 |
49 |
56 |
63 |
| A |
NOTE: 1 STEAM OUTLET
SIZE 150 PSI |
4 |
4 |
4 |
4 |
4 |
4 |
A |
| A |
NOTE: 2 STEAM OUTLET
SIZE 15 PSI |
8 |
8 |
8 |
8 |
8 |
8 |
A |
| D |
FEEDWATER CONNECTION
SIZE |
1 1/4 |
1 1/4 |
1 1/4 |
1 1/4 |
1 1/4 |
1 1/4 |
D |
| E |
BOTTOM BLOWDOWN SIZE
HIGH PRESS. |
1 1/2 |
1 1/2 |
1 1/2 |
1 1/2 |
1 1/2 |
1 1/2 |
E |
| E |
BOTTOM BLOWDOWN SIZE
LOW PRESS. & HW |
2 |
2 |
2 |
2 |
2 |
2 |
E |
| F |
STACK OUTLET SIZE O.D. |
16 |
16 |
16 |
16 |
16 |
16 |
F |
| G |
FURNACE O.D. |
32 |
32 |
32 |
32 |
32 |
32 |
G |
| H |
SHELL I.D. |
60 |
60 |
60 |
66 |
66 |
66 |
H |
| I |
SUPPY HEIGHT |
81 3/4 |
81 3/4 |
81 3/4 |
88 3/4 |
88 3/4 |
88 3/4 |
I |
| J |
WIDTH WITHOUT TRIM |
66.5 |
66.5 |
66.5 |
72.5 |
72.5 |
72.5 |
J |
| K |
WIDTH WITH TRIM |
79 |
79 |
79 |
85 |
85 |
85 |
K |
| L |
SKID WIDTH |
48 |
48 |
48 |
51 |
51 |
51 |
L |
| M |
END OF SKID TO FRONT
PLATE |
26 1/4 |
26 1/4 |
26 1/4 |
26 1/4 |
26 1/4 |
26 1/4 |
M |
| N |
SHELL TO FLOOR |
15 |
15 |
15 |
16 |
16 |
16 |
N |
| O |
SKID LENGTH |
144 |
144 |
144 |
144 |
144 |
144 |
O |
| P |
STACK OUTLET HEIGHT |
82 |
82 |
82 |
89 |
89 |
89 |
P |
| Q |
BLOWDOWN LOCATIONS |
27 13/16-94 |
27 13/16-94 |
27 13/16-94 |
27 13/16-94 |
27 13/16-94 |
27 13/16-94 |
Q |
| R |
STEAM OUTLET LOCATION.
(15 PSI & UP) |
62 5/16 |
62 5/16 |
62 5/16 |
62 5/16 |
62 5/16 |
62 5/16 |
R |
| S |
SUPPLY LOCATION |
36 13/16 |
36 13/16 |
36 13/16 |
36 13/16 |
36 13/16 |
36 13/16 |
S |
| T |
RETURN LOCATION |
102 13/16 |
102 13/16 |
102 13/16 |
102 13/16 |
102 13/16 |
102 13/16 |
T |
| U |
BURNER PROJECTION, (FROM
FRONT PLATE) |
44 |
44 |
44 |
44 |
44 |
44 |
U |
| V |
TUBE REMOVAL, FRONT |
121 |
121 |
121 |
121 |
121 |
121 |
V |
| W |
STACK OUTLET LOCATION |
136 13/16 |
136 13/16 |
136 13/16 |
136 13/16 |
136 13/16 |
136 13/16 |
W |
| X |
APPROX. OVERALL LENGTH
(STD. BURNER) |
192 |
192 |
192 |
192 |
192 |
192 |
X |
| Y |
1 1/4" SURFACE
BLOW-OFF CONNECTION |
50 5/16 |
50 5/16 |
50 5/16 |
50 5/16 |
50 5/16 |
50 5/16 |
Y |
| |
APPROXIMATE SHIPPING
WEIGHT - 150 PSI LBS. |
10050 |
10050 |
10150 |
10850 |
10850 |
10850 |
|
| APPROX. SHIPPING WEIGHT
- 15 & 30 PSI LBS. |
9250 |
9250 |
9350 |
10050 |
10050 |
10050 |
| WATER CAPACITY AT NWL
GAL. |
685 |
685 |
685 |
893 |
893 |
893 |
| WATER CAPACITY FLOODED
GAL. |
885 |
885 |
885 |
1187 |
1187 |
1187 |
| |
BOILER
HORSEPOWER |
100 |
125 |
150 |
175 |
200 |
225 |
|